Permit Number: T20CM03930
Parcel: 12714003F

Address:
373 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM03930
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2020 LOREN MAKUS ENGINEERING REVIEW Passed
06/25/2020 JPEELDA1 FIRE REVIEW Approved
06/25/2020 ALEXANDRA HINES ZONING REVIEW Approved
07/17/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/24/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets A1, A2-1, A2-2, A2-3, A2-4, A3-1, A3-2, S1, and S2: Please provide the signed, dated seal of the registered professional on these sheets.
2. Structural Calculations: The drilled pier design for Canopy G was not included in the calculations. Please provide.
3. General: Please provide the Special Inspection Certificate with Parts A and B completed.
4. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2020 JGARCIA1 APPROVAL SHELF Completed
08/26/2020 JGARCIA1 OUT TO CUSTOMER Completed
08/26/2020 JGARCIA1 REJECT SHELF Completed