Review Details: RESUBMITTAL
Permit Number - T20CM03686
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/17/2020 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Sheet C3.1 does not show the location of the water meter, reduced pressure backflow assembly and most of the route of the water service to the building. Provide a site plan that shows this information. [Initial comment: Provide the site plan referenced on sheet P1.1 showing the location of the water meter, reduced pressure backflow assembly and the route of the water service to the building. Specify the material of construction for the water service pipe. Reference: Section 107.2.1, IBC 2018.] |
| 09/24/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: Headhouse Greenhouse T20CM03686 Building Plans (2nd Review) TRANSMITTAL DATE: September 24, 2020 The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 1. Zoning acknowledges that this comment should have been provided on the 1st review. Demonstrate on the plan how the requirements of UDC Article 4.9.9.E. 2.l & .m are met. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |