The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T20CM03670
Parcel: 12714003F

Address:
373 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM03670
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2020 JPEELDA1 FIRE REVIEW Approved
06/25/2020 JOHN VAN WINKLE ENGINEERING REVIEW Approved [done - AHines2] approval of DP19-0316 required
06/25/2020 ALEXANDRA HINES ZONING REVIEW Approved [done] approval of DP19-0316 required
07/06/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/15/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 1 of 23; Scope of Work: The total SF as indicated (23,842 SF) does not match the sum of the individual canopies shown (26,748 SF). It appears the SF indicated for Canopy E (4917 SF) might be in error. Please coordinate.
2. Sheet A2-3; Canopy E: It appears on Sheet 2 of 24 that the Canopy E is split in E and F. Please coordinate.
3. Sheet A2-3; Canopy F: Please revise this canopy title to G per Sheet 2 of 24.
4. Sheet S1; Purlin Section 104: Please indicate the gauge of the purlin on this section.
5. General: Please provide the Special Inspections Certificate with Parts A and B completed.
6. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2020 SBEASLE1 OUT TO CUSTOMER Completed