Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM03670
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 06/25/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved | [done - AHines2] approval of DP19-0316 required |
| 06/25/2020 | ALEXANDRA HINES | ZONING | REVIEW | Approved | [done] approval of DP19-0316 required |
| 07/06/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/15/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet 1 of 23; Scope of Work: The total SF as indicated (23,842 SF) does not match the sum of the individual canopies shown (26,748 SF). It appears the SF indicated for Canopy E (4917 SF) might be in error. Please coordinate. 2. Sheet A2-3; Canopy E: It appears on Sheet 2 of 24 that the Canopy E is split in E and F. Please coordinate. 3. Sheet A2-3; Canopy F: Please revise this canopy title to G per Sheet 2 of 24. 4. Sheet S1; Purlin Section 104: Please indicate the gauge of the purlin on this section. 5. General: Please provide the Special Inspections Certificate with Parts A and B completed. 6. General: Please provide written responses to all review comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/28/2020 | SBEASLE1 | OUT TO CUSTOMER | Completed |