Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM03626
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 06/18/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/18/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plans sealed by an Arizona Registrant. The plans shall indicate the total roof area, the locations and sizes of the skylights. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Demonstrate energy code compliance for the addition of the skylights to the building. Reference: Sections C402.4 and 503.3.3, IECC 2018. |
| 06/18/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/02/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 07/07/2020 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 07/07/2020 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 07/13/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: The IBC Section 107 requires construction documents to be prepared by an Arizona registered design professional. Drawings required for this permit will include a last approved site plan with the building located on that site, a roof plan indicating dimensioned skylight locations, and construction details for the skylights as required. 2. General: Please provide a project valuation (labor + materials). |
| 07/13/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |