Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM03183
Parcel: 12308070B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM03183
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2020 MALLORY RESS ZONING REVIEW Approved
05/27/2020 MARTIN BROWN FIRE REVIEW Approved
05/27/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide for GFI protection for ALL single phase receptacles rated 150 volts to ground, 50 amps or less in the kitchen and food prep areas, Per NEC 210.8B.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
05/27/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS1; Code Study (Occupancy Group): The drawing indicates a "B occupancy group (Assembly less than 2500 SF)". The IBC Section 303.1.1 indicates a space used for assembly purposes with an occupant load of less than 50 persons shall be classified as a Group B. Please see Comment 2.
2. Sheet TS1; Code Study (Occupant Load): The occupant load of the Patio (29) should be included in the total occupant load, which results in 77 total occupants. The Occupancy Classification would now be an A-2. Please indicate this additional occupant load on the drawing, and revise the Occupancy Classification as required.
3. Sheet TS1; Code Study (Plumbing Fixture Requirements): Please revise the required lavatories to 1M, 1W. An appeal must be made to the Building Official for the common lavatories for the men and the women.
4. Sheet TS1; Code Study (Plumbing Fixture Requirements): Please indicate the calculations for the plumbing fixtures per the IBC Table 2902.1. For the restaurant classification, indicate the men's required water closets as 39 occupants/75 = 1 men's watercloset. Do this for all fixtures for men and women.
5. Sheet A1; Floor Plan: Per the IBC Section 1109.11, where seating or standing space is provided in accessible spaces, at least 5% of the seating and standing spaces shall be accessible. Please indicate a calculation on this sheet for the required number of those spaces, and indicate them on the Floor Plan.
6. General: Please provide a Special Inspection Certificate with Parts A and B completed. This certificate may be found on www.tucsonaz.gov/PDSD.
7. General: Please provide written responses to all review comments.
05/27/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/28/2020 JOHN VAN WINKLE ENGINEERING REVIEW Passed
06/04/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change For public toilet facilities, the required lavatory shall be located in the same room as the water closet. Reference: Section 405.3.2, IPC 2018.
06/04/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide air for combustion, ventilation and dilution of the flue gases for the relocated water heater. Reference: Section 304, IFGC 2018.
2. Show that the termination of the gravity vent for the gas-fired water heater complies with the requirements of Section 503.6.5, IFGC 2018.
06/05/2020 ROBERT SHERRY WATER REVIEW Completed