| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/15/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Designing the site Electrical constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide a complete detailed line diagram, include; (a) All feeder conduit, conductor sizes and types, amount of conductors in conduits. (b) All OCPD's sizes and types. (c) AIC ratings for the electrical service equipment and associated downstream equipment. (d) Complete panel schedules including load calculations. Also total load for the service. (e) Location on the premises of all the electrical equipment. 3. If there will be loads or equipment connected to the panel and the 100 amp disconnect at this time, please include this in the plans. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |