Permit Number: T20CM02757
Parcel: 106050440

Address:
410 W SIMMONS RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T20CM02757
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/03/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/04/2020 ROBERT SHERRY WATER REVIEW Completed
11/04/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The fixture drain and wall cleanout for P-4 are shown as 2" on the waste riser diagram but 3" on the plumbing plan. [Initial comment: Coordinate the waster riser diagram with the waste floor plan (e.g. vent sizes). Reference: Section 107.2.1, IBC 2018.]
11/04/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The submitted COMcheck envelope compliance certificate is labeled "FAIL"; the attached mechanical and lighting certificates are incomplete and unnecessary. [Initial comment: Demonstrate energy code compliance for the alterations to the building envelope using calculations based on the current code. Reference: Sections C103.2, C303, C503.1, and C503.3, International Energy Conservation Code 2018.]