Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM02757
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/19/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet x1; Exiting Plan: Per the IBC Section 1017.3, the measurement of the exit access travel distance shall be measured along horizontal and vertical paths. Please revise. 2. Sheet x1; Exiting Plan: The occupant load is calculated as 9, but the plan has indicated five rooms with 2 occupants each, and one room with 1 occupant (11 total). Please verify. 3. Sheet dm1; Demolition Plan Keynotes: It appears on the plan that the north and east exterior walls of the Breakroom are to be demolished. Please add a keynote. 4. Sheet gsn; Foundations: Note 12 references the 2012 IBC. Please revise. 5. Sheet gsn; Framing: Note 35 references the 2012 IBC. Please revise. 6. Sheet gsn; Framing: Note 41 references the IRC. Please revise. 7. Sheet s2; Framing Keynotes: Please indicate the glue lam beam size in Note 4, or add a reference for that information. 8. Sheet d2; Details 1 and 9: Please indicate the dimension for the top chord extension of the new roof trusses. 9. Sheet a1; Wall Legend: Please provide the steel stud gauge in Wall Type C, or add a reference for that information. 10. Sheet a1; Wall Legend: Please provide the size and spacing of the wall reinforcing in the new CMU wall. 11. General: Please provide structural calculations for this project. 12. General: Please provide the Special Inspection Certificate with Parts A and B completed. 13. General: Please provide written responses to all review comments. |
| 06/19/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/24/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 07/06/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. General note #4 on sheet p1 references the 2012 IPC. 2. Show the location of the gas meter on the plans. Reference: Section 107.2.1, IBC 2018. 3. Coordinate the plumbing fixture schedule entries with the plumbing notes (e.g. notes 9, 16, 19, 20, and 23). Reference: Section 107.2.1, IBC 2018. 4. Coordinate the waster riser diagram with the waste floor plan (e.g. vent sizes). Reference: Section 107.2.1, IBC 2018. 5. Show the return piping for the recirculated hot water for the water heater on the plans as noted on the water heater detail. Reference: Section 107.2.1, IBC 2018. 6. Provide equipment data for the water heater and recirculating pump. (Clarify how the recirculation pump is optional.) Reference: Section 107.2.1, IBC 2018. 7. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. 8. Verify that a cleanout is provided at the junction of the building drain and the building sewer. Reference: Section 708.1.3, IPC 2018. 9. Provide air for combustion, ventilation and dilution of the flue gases for the proposed water heater. Reference: Section 304, IFGC 2018. 10. Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 402.2, IFGC 2018. 11. Specify the type of venting systems and the venting materials to be used for the proposed water heater. Reference: Section 503.1, IFGC 2018. 12. Show the location of the water heater vent on the roof plan. Show that it complies with the termination requirements of Section 503.6.5, IFGC 2018 and Section 401.4, IMC 2018. |
| 07/06/2020 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size and serial number of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. |
| 07/06/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The 2018 International Mechanical and International Energy Conservation Codes with Local Amendments are the relevant codes for this project, not the 2012 IMC or the 2012 IRC (see Mechanical Notes #1 and #19). 2. Demonstrate energy code compliance for the alterations to the building envelope using calculations based on the current code. Reference: Sections C103.2, C303, C503.1, and C503.3, International Energy Conservation Code 2018. 3. Provide specifications for the new rooftop unit. Show that the proposed rooftop unit meets the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018. 4. Show that the rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.4.2 through C403.4.2.3, IECC 2018. 5. Provide heating and cooling load calculations to justify the heating/cooling capacity of the specified HVAC unit. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 6. The roof insulation noted on sheet a1 does not agree with the details on sheet d2. Coordinate the information. 7. Show the size, routing, and termination of the condensate drain for the rooftop unit. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson. 8. Show the location of exhaust fan EF-1 on the roof plan. Reference: Section 107.2.1, IBC 2018. 9. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018. 10. Provide the balancing data for the three exhaust registers. Reference: Section 107.2.1, IBC 2018. 11. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018. |
| 07/06/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 07/08/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/13/2020 | JGARCIA1 | APPROVAL SHELF | Completed |
| 10/13/2020 | JGARCIA1 | OUT TO CUSTOMER | Completed |
| 10/13/2020 | JGARCIA1 | REJECT SHELF | Completed |