Permit Number: T20CM02722
Parcel: 13213075A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T20CM02722
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2022 STEVE SHIELDS ZONING REVIEW Approved
08/15/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T20CM02722 rev1

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Denied
1. A corridor damper shall be installed in corridor ceiling enclosure on all floors on sheet M101 (IMC2018,607.5.4) No response to this correction Not Complied
2.Provide corridor dampers where ducts penetrate corridor ceiling enclosure throughout on 1st floor on sheet M201 (IMC2018,607.5.4) Nothing changed Not Complied
3. Provide duct smoke detector for FCU-1 and 4 they both share common duct of, of the outside air louver on sheet M201 (IMC2018,606.2.2) Nothing changed Not Complied


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E006 Panel schedule calls out for 42 KAIC rating, but Arc fault table calls out for 22 KAIC and actual Arc Fault calculation is only 6,514 amps ie even a 10 KAIC panel is acceptable.
E301 Equipment shed plan needs to use panel P for lighting and receptacle power circuits and not use Panel H1B. This conflicts with NEC Code 225.30.


PLUMBING REVIEW COMMENTS:
Denied
FIRST PLUMBING REVISION REVIEW:
1). DETAIL B ON A001 SHOW OPEN ROOF ON PORTION OF EQUIPMENT SHED, SANITARY FLOOR DRAIN & POOL DRAIN ON P100 & P101 CAN'T RECEIVE STORM WATER. -IPC 1101.3


If you require a dditional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/16/2022 VVERA1 OUT TO CUSTOMER Completed