Permit Number: T20CM02722
Parcel: 13213075A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02722
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T20CM02722


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Denied
Correction #3 not complied recirculating hood are not acceptable must have exhaust to the outdoors per chapter 4 Not Complied there is no radiation damper tested and listed for kitchen exhaust applications
Correction #4 Complied
Correction #8 Show in a plan view how you are protecting fire rated ceiling penetrations of the heating and cooling ducts in all apartments and 1st floor ceiling penetrations on sheet M-201 (IMC2018,607.6.2) Complied See new violation below
A corridor damper shall be installed in corridor ceiling enclosure on all floors on sheet M101 (IMC2018,607.5.4)
Provide duct smoke detector for FCU-1 and 4 they both share common duct of, of the outside air louver on sheet M201 (IMC2018,606.2.2)
Provide corridor dampers where ducts penetrate corridor ceiling enclosure throughout on 1st floor on sheet M201 (IMC2018,607.5.4)
Elevator machine rooms, machinery spaces that contain the driving machine, and control rooms or spaces that contain the operation or motion controller for elevator operation shall be provided with an independent ventilation or air-conditioning system to protect against the overheating of the electrical equipment. show where you are providing this (IBC2018,3005.2)
ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved
02/01/2022 STEVE SHIELDS ZONING REVIEW Approved