Permit Number: T20CM02722
Parcel: 13213075A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02722
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T20CM02722

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. Correction #1 complied
2. Correction #2 complied
3. Correction #3 not complied recirculating hood are not acceptable must have exhaust to the outdoors per chapter 4
4. Correction #4 not complied, you cant use a ceiling radiation damper into a dryer duct, Morgan advanced materials has the shaft product listed for dryer shaft.
5.Correction #5 complied
6. Correction #6 complied
7. Correction #7 complied
8. Show in a plan view how you are protecting fire rated ceiling penetrations of the heating and cooling ducts in all apartments and 1st floor ceiling penetrations on sheet M-201 (IMC2018,607.6.2)
ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved
10/08/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
10/08/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Waterwalk Corporate Lodging @ Tucson Marketplace
New Hotel – PAD-15
T20CM02722 (2nd Review)

TRANSMITTAL DATE: October 8, 2021

1. Zoning has reviewed the building plan for compliance with DP20-0039 and although the building plans match the DP Zoning will not approve until approved by all PDSD Review Staff.

2. The development package sheets provided in the drawing set either need to be: 1) the approved stamped sheet, 2) marked as for reference only or 3) removed for the drawing set.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
10/19/2021 ROBERT SHERRY WATER REVIEW Completed
10/25/2021 JPEELDA1 FIRE REVIEW Approved