Permit Number: T20CM02722
Parcel: 13213075A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T20CM02722
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2020 JPEELDA1 FIRE REVIEW Reqs Change IFC 2018, 507.5.1.1 Hydrant for standpipe systems. Buildings equipped with a standpipe system installed in accordance with Section 905 shall have a fire hydrant within 100 feet of the fire department connections.
Notes for testing: IFC 2018, Section 510, Emergency Responder Radio Coverage. 510.1 Emergency responder radio coverage in new buildings. New buildings shall have approved radio coverage for emergency responders within the building based on the existing coverage levels of the public safety communication system utilized by the jurisdiction, measured at the exterior of the building.
IFC 2018, 1009.8 Two-way Comunication. A two-way communication system complying with Section 1009.8.1 and 1009.8.2 shall be provided at the landing serving each elevator or bank of elevators on each accessible floor that is one or more stories above or below the level of exit discharge.
IBC 2018, 3001.2, Emergency elevator communication system for the deaf, hard of hearing and speech impaired. An emergency two-way communication system shall be provided that:
1. Is a visual and text-based and video-based 24/7 live interactive system
2. Is fully accessible by the deaf, hard of hearing and speech impaired, and shall include voice-only options for hearing individuals.
3. Has the ability to communicate with emergency personnel utilizing exisitng video conferencing technology, chat/text software or other approved technology
07/27/2020 ARUIZ1 PLUMBING-COMMERCIAL REVIEW Needs Review
07/27/2020 ARUIZ1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/27/2020 ARUIZ1 ZONING REVIEW Needs Review
07/27/2020 ARUIZ1 BUILDING-COMMERCIAL REVIEW Needs Review
07/27/2020 ARUIZ1 WATER REVIEW Needs Review
07/27/2020 ARUIZ1 MECHANICAL-COMMERCIAL REVIEW Needs Review
07/27/2020 ARUIZ1 ENGINEERING REVIEW Needs Review
07/27/2020 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/27/2020 ARUIZ1 OUT TO CUSTOMER Completed