Permit Number: T20CM02530
Parcel: 13213099A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02530
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/25/2020 ROBERT SHERRY WATER REVIEW Completed
08/25/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/25/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved. Horizontal branches still connect to vertical stacks closer than ten diameters downstream of the base of the vertical stacks. [Initial comment: Horizontal branches shall connect no closer than ten diameters downstream of the bases of vertical stacks (see riser diagrams 1, 5, 6 and 7 on sheet P-5). Reference: Section 704.3, IPC 2018.]
08/26/2020 JPEELDA1 FIRE REVIEW Approved
08/26/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
Previous electrical plan review comment#
1. Could not locate 2018 IECC lighting calculations 0r Comcheck on this 2nd plan submittal. Could not verify compliance.
2. Comment #5, and response. Lamp color temperature cannot exceed 3500K for exterior lighting Sec.402.1 (OLC).
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code (OLC).
09/08/2020 SSHIELD1 ENGINEERING REVIEW Reqs Change DP must be approved first.
09/08/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: Woodspring Suites
T20CM02530
Building Plan (3rd Review)

TRANSMITTAL DATE: September 8, 2020

1. Zoning has reviewed the building plans for compliance with the submitted development package DP20-0073. While the building plans are consistent with the DP as it relates to the zoning review purview of the building footprint, building height, square footage, site conditions etc., zoning cannot approve the building plans until the DP is approved and all PDSD Commercial Plans reviewers have approved the building plans.

2. The development package sheets provided in the building plan set will either need to be the stamped approved development package sheets, marked for reference only, or removed from the building plans.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956