Permit Number: T20CM02432
Parcel: 12310001H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02432
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/08/2020 ROBERT SHERRY WATER REVIEW Completed
06/08/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/08/2020 JPEELDA1 FIRE REVIEW Approved
06/08/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The branch circuit designations do not correlate with the panel schedules. For example; Receptacles in the Temp Level 1 NEP Frozen Section called out as circuits PIC-112-5 are identified as OR Receptacles in the panel schedule. Please revise all the branch circuits to identify their locations accurately in the panel schedules. NEC 408.4
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements
06/08/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed