Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM02432
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/08/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/08/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/08/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/08/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 06/08/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The branch circuit designations do not correlate with the panel schedules. For example; Receptacles in the Temp Level 1 NEP Frozen Section called out as circuits PIC-112-5 are identified as OR Receptacles in the panel schedule. Please revise all the branch circuits to identify their locations accurately in the panel schedules. NEC 408.4 Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements |
| 06/08/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |