Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM02353
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/05/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Please explain or clarify why there are 2 Overall Site plans and 2 Electrical Lighting Calculation plans with different values in this plan set. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
05/05/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/06/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Specify the type of backflow protection devices or assemblies being applied to the "Life Support Equip" or the "Drum Filter Control Skid" and the type of hazard associated with each application. Reference: Section 608.1, IPC 2018. 2. Provide a backflow prevention assembly for the misting system. Reference: Section 608.1, IPC 2018. 3. Provide the civil plans that show the continuation of the DCW and sanitary waste lines as noted in keynotes #1 and #2 on sheet PF2.1. Refrence: Section 107.2.1, IBC 2018. 4. Verify the the FFE of the support building for the flamingo exhibit is 12" or more above the rim elevation of the next upstream manhole. Reference: Section 714.1, IPC 2018. |
05/06/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Show that the proposed new buildings and the alterations to existing buildings comply with the energy requirements for the building envelopes (e.g. COMcheck envelope compliance certificate). 2. Provide heating/cooling load calculations for the new packaged air conditioner, RTU-E1. |
05/06/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/07/2020 | ELISA HAMBLIN | ZONING | REVIEW | Approved | |
05/27/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
06/12/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet AE0.1; Code Review Plan; Occupancy Table: The existing SF in the Occupancy Table for Booths 1, 2, and 3, and for the Office 4, do not match the SF shown on the Code Review Plan. Please verify. 2. Sheet AE0.1; Code Review Plan; Occupancy Table: In the Occupancy Table, a new area of 314 SF is indicated in "Membership 5". Please verify the SF of that area. 3. Sheet AE0.1; Occupancy Table: The "Membership 5" area uses 50 SF/occupant. Please indicate which Function of Space was used in the IBC Table 1004.5. 4. Sheet SE0.1; General Structural Notes: Note 8 indicates the footing design is based upon minimumIBC soil bearing values in the absence of a soil report. There is an original soil report and an addendum to that report. Please review these reports and revise this note as required. 5. Sheet SE2.2 (Roof Framing Plan); Structural Calculations (Page 3 of 87): A cross beam (exterior column to the existing wall) in the calculations indicates a B1 beam (6x12), while the Roof Framing Plan indicates a B2 (4x8). Please coordinate. 6. Sheet SF1.1; Low Roof Framing Plan: Please indicate the roof joist size, or reference it to the schedule on Sheet SF6.1. 7. General: Please provide a Special Inspection Certificate with Parts A and B completed. 8. General: Please provide written responses to all review comments. |