Permit Number: T20CM02241
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02241
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2020 ELISA HAMBLIN ZONING REVIEW Approved
04/14/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/14/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/14/2020 EHAMBLI1 ENGINEERING REVIEW Passed
04/14/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/14/2020 ROBERT SHERRY WATER REVIEW Completed
04/14/2020 MARTIN BROWN FIRE REVIEW Approved
04/16/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet g2.0; Code Analysis: The Type of Construction is indicated as Type I-2 with a reference to Table 503. Please revise the reference and change the Construction Type per the IBC Chapter 6.
2. Sheet g2.0; Code Analysis: The Remodel Area indicates the Gym Space as 2559 SF, while the Occupant Load indicates 2259 SF. Please verify.
3. Sheet a2.0; Reflected Ceiling Plan: Please indicate all new and existing exit signs on this plan.