| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/14/2020 | ELISA HAMBLIN | ZONING | REVIEW | Approved | |
| 04/14/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/14/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/14/2020 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
| 04/14/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/14/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/14/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/16/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet g2.0; Code Analysis: The Type of Construction is indicated as Type I-2 with a reference to Table 503. Please revise the reference and change the Construction Type per the IBC Chapter 6. 2. Sheet g2.0; Code Analysis: The Remodel Area indicates the Gym Space as 2559 SF, while the Occupant Load indicates 2259 SF. Please verify. 3. Sheet a2.0; Reflected Ceiling Plan: Please indicate all new and existing exit signs on this plan. |