Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T20CM02240
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/23/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet g1.0; State Health Codes: Please revise the ICC/A117.1 Code to the 2009 Edition. 2. Sheet a1.0; Floor Plan Sheet Legend: This Table indicates 'See Sheet Series "X" '. Please verify. 3. Sheet a1.0; Reference Floor Plan: The east wall of Restrooms 123 and 124 indicates a CH2 Wall Type. That Wall Type is not indicated on Sheet a9.0. Please verify. 4. Sheet a2.0; Reflected Ceiling Plan: It appears more directional exit signage should be located in the corridor on the east end of this space leading to the south exit. Please verify. 5. Sheet a6.0; Wall Section 1: Please indicate this section on the Floor Plan (Sheet a1.0) or in a Keynote on that sheet. 6. Sheet a7.1; Wall Elevation 14: The water closet should not be indicated on this elevation. Please verify. 7. Sheet a7.2; Wall Elevation 16: The horizontal grab bar should be indicated on this elevation. Please verify. 8. General: Please provide written responses to all review comments. |
| 07/23/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/23/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. |
| 07/23/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete compliance with the 2018 IECC for the lighting. |
| 07/23/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify how the outdoor air calculation for terminal units 7, 8. 9, 10, 12, and 13 relates to the ASHRAE 170 outdoor air calculations. Reference: Section 107.2.1, IBC 2018 |