Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM02239
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The submitted calculations of the door and cooler refrigeration system for a walk-in cooler do not address the code requirements. The requirement for the refrigeration system efficiency (Table C403.10.2.1 (3), IECC 2018) requires the ratio of the total heat (in BTU) removed from the walk-in box during a 1-year usage period to the total energy input of the refrigeration system in Watt-hours during the same period. The maximum energy consumption of a door for walk-in cooler is based not only on the R-value of the door's insulation but on the gaskets and sweeps for the door. [Initial comment: Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018.] |