Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/17/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
03/17/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. When using Table 402.4 (2), IFGC 2018 to determine the size of the gas pipes, a developed length of 258-feet requires the 300-feet line of the table to be used. A 2" carbon steel pipe can accommodate only 638 CFH at 300-feet. 2. Correct the keynote associated with equipment #11 on detail 2/P1. 3. Keynote #13 on sheet P1 refers to an existing hood. Revise to indicate that the hood is being installed as part of this activity. 4. Keynote #2 on sheet P1 calls for the vent to run horizontally before it is 6" above the flood rim of the grease interceptor. This exception to Section 905.4, IPC 2018 is only applicable to grease interceptors located outdoors. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/16/2020 | LBOWERS1 | REJECT SHELF | Completed |