Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM01306
Parcel: 11712033A

Address:
17 N STONE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM01306
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/17/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. When using Table 402.4 (2), IFGC 2018 to determine the size of the gas pipes, a developed length of 258-feet requires the 300-feet line of the table to be used. A 2" carbon steel pipe can accommodate only 638 CFH at 300-feet.
2. Correct the keynote associated with equipment #11 on detail 2/P1.
3. Keynote #13 on sheet P1 refers to an existing hood. Revise to indicate that the hood is being installed as part of this activity.
4. Keynote #2 on sheet P1 calls for the vent to run horizontally before it is 6" above the flood rim of the grease interceptor. This exception to Section 905.4, IPC 2018 is only applicable to grease interceptors located outdoors.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/16/2020 LBOWERS1 REJECT SHELF Completed