Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T20CM01263
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 01/25/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 02/01/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/03/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet E0.1. The exterior luminaire schedule shows the lamp color temperature at 4000K for the 'SH' luminaire. The maximum allowed per section 402.1 of the OLC is 3500K. Please indicate all the exterior luminaires lamp color temperature output. 2. For clarity, please indicate what electrical or mechanical equipment is new or changed and what was shown per the original approved plan. 3. Please indicate new or changed/added loads on the panel schedules. 4. Please provide quantities of equipment on the mechanical schedule. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC). |
| 02/04/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | UNTIL THE REVISION TO DP19-0147 HAS BEEN APPROVED THE REVISION TO THE BUILDING PLAN CANNOT BE APPROVED. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/22/2021 | LBOWERS1 | OUT TO CUSTOMER | Passed |