Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM01263
Parcel: 13711425E

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T20CM01263
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2020 MARTIN BROWN FIRE REVIEW Approved
03/05/2020 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T20CM01263- New Storage Building (Storage Use Group - Personal Storage Building)
Building Plan Review (1st Review) Irvington Nineteen Storage
1760 W Irvington Road - C-1 Zoning - Related to DP19-0147

TRANSMITTAL DATE: March 5, 2020

DUE DATE: March 20, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has done a review of the building plans. While the building plans are consistent with what has been approved on the development plan DP19-0147 and consistent as it relates to the zoning review purview, zoning cannot approve the building plans at this time.

One item that needs to be addressed on the building plans are the site sheets. Per the site sheets of the building plan set it appears that a landscape island is proposed along the northeast parking area. There does not appear to be a Landscape island on the approved DP. Revise the building site sheets that include the landscape island.

If the DP sheets are to be included in the building package they must be the PDSD approved and signed copies. Remove the unapproved version of the DP sheets from the building package or mark them as "Reference only, see the PDSD approved and signed DP package DP19-0147".


2. COMMENT: Zoning will review the building plans on the next submittal to assure consistency with the approved and signed copy of the DP. (If any changes are necessary to the building plans due to plan review comments that affect zoning requirements the DP will have to be revised to reflect the changes.)

Once the building plans are approved by the Commercial Plans reviewers zoning can approve the building plans.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans
03/10/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet T1.0 under Code Analysis - Chapter 29 - Office states 1/100 for water closets and 1/100 for lavatories , and Storage states 1/300 for water closets and 1/300 for lavatories . Amend plan using the correct number for male and female occupants for mininum required water closets and lavatories .IBC Chap 29.
2.Sheet AO.2 under - Building Occ Calcs - states Basement Level , but the sheet is for the First Floor Exit Plan . Amend plan sheet . IBC107.2.1.
3. Sheet AO.2 under - Building Occ Calcs - states Basement Level , but the sheet is for the Second Floor Exit Plan . Amend plan sheet . IBC107.2.1.
03/25/2020 LOREN MAKUS ENGINEERING REVIEW Approved
03/31/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change All exterior lighting must comply with the City of Tucson / Pima County Outdoor Lighting Code . COT.
04/27/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the size of the water service pipe to limit the water velocity to no more than recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper). Reference: Sections 303.2 and 604.3, IPC 2018.
2. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
04/27/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the COMcheck Mechanical Compliance Certificate to show the building located in Tucson, Arizona.
2. Provide ventilation for the office area. Reference: Sections 401.2 and 401.3, IMC 2018.
3. Revise the sequence of operation for the restroom exhaust fan so that all the air supplied to the restrooms will be exhausted (i.e. all the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.
04/27/2020 ROBERT SHERRY WATER REVIEW Reqs Change Revise the water calculations based on the additional demand caused by increasing the minimum number of plumbing fixtures required by Section 2902.1, IBC 2018.
06/28/2020 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2020 ARUIZ1 OUT TO CUSTOMER Completed