Permit Number: T20CM01163
Parcel: 12419040D

Address:
555 S CHERRY AV

Review Status: Completed

Review Details: OTHER

Permit Number - T20CM01163
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The FFE for building 11 (2431.50) is less than 12" above the rim elevation for the next upstream manhole (MH#3, 2430.74). Call for a backwater valve to be installed when the building is connected to the private sewer collection system. Reference: Section 714.1, IPC 2018 as amended by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2020 LBOWERS1 REJECT SHELF Completed