Permit Number: T20CM00831
Parcel: 117110210

Address:
201 N COURT AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM00831
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2020 MARTIN BROWN FIRE REVIEW Approved
02/27/2020 DJELLEN1 ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Steve Shields
Section Manager


PROJECT:
T20CM00831
201 N Court Avenue Description
Roof Mounted Solar

TRANSMITTAL: February 5, 2020
COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

This site is located in the HC-3 zone (UDC 4.7.22).

Historic review required for roof mounted solar.
03/05/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
03/11/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan recommends. Also provide a written response.
1. Provide a grounding detail for the rack and module grounding.
2. Show the location of the 100 amp sub-panel.
3. Provide an elevation detail that shows the inverter and sub-panel mounting.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/06/2020 KROBLES1 APPROVAL SHELF Completed
04/06/2020 KROBLES1 OUT TO CUSTOMER Completed
04/06/2020 KROBLES1 REJECT SHELF Completed