Permit Number: T20CM00700
Parcel: 127080120

Address:
5410 E 5TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM00700
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T19CM00700
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on each sheet of the plans.

SECTIONS - DETAILS:

1. A vented attic space requires a calculation for showing the attic ventilation opening size using 1 to 150 of attic area in compliance with R806.2. Show appropriate attic vent size and location.

PLUMBING PLANS:

1. Provide the BTU demand of the new water heater, and verify the size of the supply pipe for the connected demand (may require upgrading), G2413.3 & Table G2413.4(1).

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review