Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
Residential Building - One or Two Family
Address:
5410 E 5TH ST
Address NEW:
5410 E 5TH ST
Apply Date:
01/30/2020
Applicant:
Description:
E - FAMILY ROOM, LAUNDRY ROOM ADDITION W/ GARAGE

Permit Reviews

Permit Number - T20CM00700
Permit Status: Expired
Permit Description: E - FAMILY ROOM, LAUNDRY ROOM ADDITION W/ GARAGE
Start Date Submittal Complete Date Status  
01/30/2020 RESIDENTIAL - BLDG/ZONING-WALKTHRU 01/30/2020 COMPLETED Review Details
01/30/2020 RESUBMITTAL 02/24/2020 COMPLETED Review Details
02/24/2020 RESUBMITTAL 02/25/2020 COMPLETED Review Details
03/16/2020 REVISION - - 1ST 02/24/2021 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T20CM00700
Permit Status: Expired
Permit Description: E - FAMILY ROOM, LAUNDRY ROOM ADDITION W/ GARAGE
Total Outstanding Activity Conditions - 1
Date Name
01/30/2020 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Conditions

Permit Number - T20CM00700
Permit Status: Expired
Permit Description: E - FAMILY ROOM, LAUNDRY ROOM ADDITION W/ GARAGE
Date Description Comments
01/30/2020 ROOF TRUSSES MUST BE APPROVED PRIOR TO FRAMING INSPECTION (P2I)

Completed Inspections

Permit Status: Expired
Permit Number: T20CM00700
Permit Description: E - FAMILY ROOM, LAUNDRY ROOM ADDITION W/ GARAGE
Total Completed Inspections - 18
Date Description Inspector Results Comments
03/06/2020 COT - RSEL - Grounding/Bonding Passed {Activity date: 03/06/2020; Status: Approved; Inspector: RCHANDLER; Comment: Entered by YLEON1 - CUSTOMER SENT PICTURES TO INSPECTOR. INSPECTOR APPROVED.} ; {Activity date: 03/04/2020; Status: Partial Approval; Inspector: RCHANDLER; Comment: Entered by SFLORES2 - Copper is too short to reach service; install longer piece or provide irreversible crimp to existing Grounding Electrode Conductor.} ; {Activity date: 03/03/2020; Status: Cancelled; Inspector: RCHANDLER; Comment: Entered by SFLORES2 - Canceled Per phone call from customer and office.} ; {Activity date: 03/02/2020; Status: Not ready for Inspection; Inspector: RCHANDLER; Comment: Entered by DMERANZ1 - Work incomplete.}
03/06/2020 COT - RSBU - Excavation/Rebar/Zoning Passed {Activity date: 03/06/2020; Status: Approved; Inspector: RCHANDLER; Comment: Entered by YLEON1 - CUSTOMER SENT PICTURES TO INSPECTOR. INSPECTOR APPROVED.} ; {Activity date: 03/04/2020; Status: Correction Required; Inspector: RCHANDLER; Comment: Entered by SFLORES2 - Two outta three is bad; still need sleeves for piping passing through footings. Customer will send pictures when completed.} ; {Activity date: 03/03/2020; Status: Cancelled; Inspector: RCHANDLER; Comment: Entered by SFLORES2 - Canceled Per phone call from customer and office.} ; {Activity date: 03/02/2020; Status: Correction Required; Inspector: RCHANDLER; Comment: Entered by DMERANZ1 - 1--Bottom of footing is less than 12" below undisturbed soil.
2-Remove all roots from footings.
3--Sleeve piping passing through footing.}
03/26/2020 COT - RSPL - Rough Soil Passed {Activity date: 03/26/2020; Status: Approved; Inspector: RCHANDLER; Comment: Entered by SFLORES2 - RVI
Corrections completed.

} ; {Activity date: 03/26/2020; Status: Approved; Inspector: RCHANDLER; Comment: Entered by SFLORES2 - RVI
Corrections completed.} ; {Activity date: 03/24/2020; Status: Cancelled; Inspector: RCHANDLER; Comment: Entered by SFLORES2 - No number on file to contact for remote inspection.} ; {Activity date: 03/23/2020; Status: Correction Required; Inspector: RCHANDLER; Comment: Entered by SFLORES2 - 1-Expose all fittings to allow 360 degree viewing.
2-No test on DWV piping.
3-Verify slope per code at laundry room.
Note: Per builder gas piping will be moved from under habitable spaces at future date.

} ; {Activity date: 03/16/2020; Status: Cancelled; Inspector: RCHANDLER; Comment: Entered by SFLORES2 - Per phone call with customer.

} ; {Activity date: 03/02/2020; Status: Not ready for Inspection; Inspector: RCHANDLER; Comment: Entered by DMERANZ1 - Work incomplete.}
04/01/2020 COT - RSBU - Preslab Passed {Activity date: 04/01/2020; Status: Approved; Inspector: TTREMBULAK; Comment: Entered by SFLORES2 - RVI} ; {Activity date: 03/03/2020; Status: Cancelled; Inspector: RCHANDLER; Comment: Entered by SFLORES2 - Canceled Per phone call from customer and office.} ; {Activity date: 03/02/2020; Status: Not ready for Inspection; Inspector: RCHANDLER; Comment: Entered by DMERANZ1 - Work incomplete.}
04/14/2020 PDSD Building Division - TEP PM Clearance Passed {Activity date: 04/14/2020; Status: Approved; Inspector: TTREMBULAK; Comment: Entered by RSALDAT1 - CODE INCR}
04/14/2020 COT - RSEL - Service Upgrade Passed {Activity date: 04/14/2020; Status: Approved; Inspector: TTREMBULAK; Comment: Entered by RSALDAT1 - RVI Clearance for TEP INCR called in to Natalie at 9:40 a.m.

}
04/23/2020 COT - RSBU - Masonry Pregrout Passed {Activity date: 04/23/2020; Status: Approved; Inspector: ESTEVENS; Comment: Entered by RSALDAT1 - Final lift for ICF} ; {Activity date: 04/20/2020; Status: Denied; Inspector: TTREMBULAK; Comment: Entered by RSALDAT1 - RVI No contact information

Contact information needed. Please call your inspector for further inspection information

} ; {Activity date: 04/17/2020; Status: Partial Approval; Inspector: BSTEVENS; Comment: Entered by BSTEVENS - RVI
OK TO 6'} ; {Activity date: 03/04/2020; Status: Not ready for Inspection; Inspector: RCHANDLER; Comment: Entered by SFLORES2 - Work incomplete.} ; {Activity date: 03/02/2020; Status: Not ready for Inspection; Inspector: RCHANDLER; Comment: Entered by DMERANZ1 - Work incomplete.}
06/05/2020 COT - RSBU - Roof Nailing Passed {Activity date: 06/05/2020; Status: Approved; Inspector: WGALLAGHER; Comment: Entered by RSALDAT1 - }
06/05/2020 COT - LCBU - Framing Passed {Activity date: 06/05/2020; Status: Approved; Inspector: WGALLAGHER; Comment: Entered by RSALDAT1 - }
06/30/2020 COT - BULD - SWG Clearance Passed {Activity date: 06/30/2020; Status: Approved; Inspector: TTREMBULAK; Comment: Entered by RSALDAT1 - CODE}
06/30/2020 COT - RSPL - Gas Pressure Test Passed {Activity date: 06/30/2020; Status: Approved; Inspector: TTREMBULAK; Comment: Entered by RSALDAT1 - Approved. Clearance for SWGAS connect ok.} ; {Activity date: 03/02/2020; Status: Not ready for Inspection; Inspector: RCHANDLER; Comment: Entered by DMERANZ1 - Work incomplete.}
07/20/2020 COT - RSPL - Yard Water Line Passed {Activity date: 07/20/2020; Status: Approved; Inspector: WGALLAGHER; Comment: Entered by JSCHNEI2 - Approved}
08/11/2020 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed {Activity date: 08/11/2020; Status: Approved; Inspector: TTREMBULAK; Comment: Entered by RSALDAT1 - Approved}
02/18/2021 COT - RSEL - Outdoor Lighting Passed {Activity date: 02/18/2021; Status: Approved; Inspector: DQUINN; Comment: Entered by RSALDAT1 - Ap
}
02/18/2021 COT - RSEL - Electrical Final Passed {Activity date: 02/18/2021; Status: Approved; Inspector: DQUINN; Comment: Entered by RSALDAT1 - Ap
}
06/28/2021 COT - RSME - Mechanical Final Passed {Activity date: 06/28/2021; Status: Approved; Inspector: RELEFANTE; Comment: Entered by VLEON1 - }
06/28/2021 COT - RSPL - Plumbing Final Passed {Activity date: 06/28/2021; Status: Approved; Inspector: RELEFANTE; Comment: Entered by VLEON1 - }
10/15/2021 RSBU - Building Final Passed {Activity date: 10/15/2021; Status: Approved; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - Approved} ; {Activity date: 06/28/2021; Status: Denied; Inspector: RELEFANTE; Comment: Entered by VLEON1 - DE( grate needs cover plated and fixtures installed and also fire rated door)}

Documents

File Name Document Type  
APPLICATION.PDF DOCUMENTS VIEW
PERMIT.PDF DOCUMENTS VIEW
OWNER BUILDER WAIVER.PDF DOCUMENTS VIEW
JOB CARD.PDF DOCUMENTS VIEW
TRUSSES.PDF DOCUMENTS VIEW
PLAN SET.PDF CONSTRPLANS VIEW
REV1_PLAN.PDF CONSTRPLANS VIEW