Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T20CM00360
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/04/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The approved variance request letter from Pima County Wastewater Reclamation calls for the installation of a 6" x 8" wye connection of the building sewer to the existing 8" public sewer. Sheet P2.1A shows an 8" building sewer and refers to civil plans for the continuation of the building sewer to the public sewer. Verify that the connection of the 8" building sewer to the public sewer is still approved by Pima County Wastewater Reclamation. Provide the civil plans showing the connection to the public sewer. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/01/2021 | LBOWERS1 | OUT TO CUSTOMER | Passed |