Permit Number: T20CM00360
Parcel: 117062070

Address:
127 S 5TH AV

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T20CM00360
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2020 MARTIN BROWN FIRE REVIEW Reqs Change Add note to plans indicating installation of fire sprinklers, fire sprinkler underground supply piping, and fire alarm systems are a deferred submittal.
Indicate on sheet A 0.2 that the "mechanical room" is in fact the fire pump room.
Please review section 4.13.1.1 of the 2016 edition of NFPA 20. Confirm only fire pump related equipment and equipment related to domestic water distribution aer in the pump room.
Please review 4.13.2.1.1 of the 2016 NFPA 20, and indicate on plans the required RATED passageway.
02/12/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Correct keynote #30 on sheet P2.1A where the 6" ORWL changes to a 3" soil pipe (UG).
02/12/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. As well as AFCI protection for branch circuit protection, also provide for GFCI protection for personal for the dishwasher and laundry outlets. NEC 210.8A (10), 210.8D.
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements.
02/12/2020 DAVID RIVERA ZONING REVIEW Reqs Change Common Building Notes

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T20CM00360- New Building (Residential Use - Multi-Family)
Building Plan Review (1st Review) 127 S 5Th Avenue
127 S 5Th Avenue - C-3 Zoning - Related to DP19-0122

TRANSMITTAL DATE: February 12, 2020

DUE DATE: February 21, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package. While the building footprint is consistent with the approved DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until the PDSD Commercial Plans reviewers and Design Professional approve the building plans.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. (Remove the unapproved version of the DP included in the Building Plan Package and add a copy of the approved and PDSD stamped version of the DP with the next building submittal.)

3. COMMENT: If any changes are necessary, due to the PDSD Commercial Plan Reviewer's or Design Professional comments that affect or change the building footprint, height, or square footage, the DP will need to be updated prior to approval of the building plans by Zoning.

4. COMMENT: Once the building plans have been reviewed and approved by the PDSD Commercial Plan Reviewers and Design Professional and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans
02/12/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change T20CM00360
1. Sheet A0.1; Building Data (Building Height): The IBC Table 504.4 indicates 12 stories are allowed and Table 504.3 indicates a 180 foot building height is allowed. Please revise the values shown on Sheet A0.1 (those are not values from the 2018 IBC).
2. Sheet A0.1; Means of Egress: This sheet indicates the total stair width required per floor is 80". Please indicate on this sheet how that requirement was calculated and the 2018 code section reference.
3. Sheet A0.1; Means of Egress: This sheet indicates the corridor width required is 40". Please indicate on this sheet how that requirement was calculated and the 2018 code section reference.
4. Sheet A0.1; Means of Egress: This sheet indicates the exit door width required per floor is 72". Please indicate on this sheet how that requirement was calculated and the 2018 code section reference.
5. Sheet A0.1; Means of Egress: The travel distance references Section 1016.2. Please revise that reference to the 2018 IBC.
6. Sheet A0.1; Means of Egress: The common path of travel references Section 1014.3. Please revise that reference to the 2018 IBC.
7. Sheet A0.1; Means of Egress: The number of exits references Section 1015.1. Please revise that reference to the 2018 IBC.
8. Sheet A0.1; Means of Egress: The exit separation references Section 1015.2.1. Please revise that reference to the 2018 IBC.
9. Sheet A0.2; First Floor Code Plan: Please indicate on this plan the distance between the two exits, and the diagonal dimension of the building. Please verify the requirements of the IBC Section 1007.1.1 (separation distances) are met.
10. Sheet A0.2; First Floor Code Plan: Please verify the door swing of the door south of the mechanical room meets the requirements of the IBC Section 1010.1.2.1.
11. Sheet A0.2; Second through Seventh Floor Code Plans: Please verify the requirements for an accessible elevator (Section 1009.2.1), elevator standby power (Section 1009.4.1), elevator two-way communications (Section 1009.8), and Chapter 30 are met.
12. Sheet A0.2; Wall Rating Legend: Please indicate a U.L. Listing Number for these walls, or reference that information (Sheet A0.3).
13. Sheet A2.1; Floor Plan: Stair 2 has an enlarged plan reference of 1+/A6.0. Please revise all plans.
14. Sheet S1.0; General Structural Notes (Foundations): Note 1 indicates a soils report was used for the foundation design. Please provide that report.
15. Sheet S1.0 (General Structural Notes); Structural Calculations (Sheet 95): The General Structural Notes indicates a basic wind speed of 110 MPH, while the calculations indicate a 105 MPH basic wind speed was used. Please coordinate and revise calculations as required.
16. Sheet S1.1; General Structural Notes (Cold-Formed Steel Framing): Note 12 indicates to reference plans/details for steel stud wall gage and spacing. Please expand this note to add specific locations of that information.
17. Sheet S1.3; Detail 21: At the 'Edge of Slab Condition', please complete the Typical Embedment Schedule Detail reference.
18. Sheet S1.4; Detail 42: Please provide structural calculations for the light pole foundation design.
19. Sheet S2.0; Foundation Plan Notes: Note 6 references a Sump Pit Detail 233. Please revise that reference.
20. Sheet S6.1; Detail 431: Please provide verbiage for a blank detail note.
21. General: Please provide a Special Inspection Certificate with Parts A and B completed. You may find this form at www.tucsonaz.gov/PDSD.
22. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
02/12/2020 ROBERT SHERRY WATER REVIEW Completed
02/12/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
02/20/2020 SKOHEN1 DESIGN PROFESSIONAL REVIEW Approved Design Professional Review Comments
Date: 14 February 2020
To: Maria Gayosso
Planning and Development Services
City of Tucson
201 N. Stone Avenue
Tucson, AZ 85701
From: R. Fe Tom, AIA
City of Tucson
Design Professional
Project: TAC # 19013: 127 S 5th Ave
T20CM000360 - DP19-0122 - T19SA00132 (IID-19-06) - 127 S. 5th Ave - Building Plans
Review
Re: Application Review Comments for 127 S. 5th Ave – Building Plans Review
The purpose of this document is to show the comments from my review. The Applicant has submitted
Construction Documents for the 7-story apartment building, permit #T20CM00360. The project has the
associated IID-19-06 and DP19-0122.
Based on the drawings provided, I have evaluated the documents for their consistency with the approved
IID requirements. I do not find any major design modifications and I have determined that the information
is consistent with the information provided in the approved IDD. As the Design Professional, I therefore
approve the design.
End of Review Comments
Richard Fe Tom, AIA
COT Design Professional
02/26/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change 1) Ensure that roof drains scupper underneath sidewalks as needed. Reference COT Technical Standards Manual (TSM) section 7-01.4.1.e. Coordinate placement of scuppers with development package
02/26/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Keynote #3 on sheet M3.0 in reference to dryer exhaust ducts states, "flex ducts as required." Explain how this complies with the requirements of Sections 504.8.1 and 504.8.2, IMC 2018.
2. The dryer exhaust duct in units 701, 702, 713, 714, and 716 appear to have an equivalent length greater than 35-feet. If the dryer manufacturer allows the 35-foot length to be exceeded, show the make and model of the proposed dryer on the plans and provide a copy of the manufacturer's installation instructions. Reference: Section 504.8.4, IMC 2018.
3. Provide calculations (e.g. COMcheck) to show that the building thermal envelope complies with the requirements R401.2, IECC 2018.
4. Provide mechanical ventilation for the residential portions of the building. Reference: Sections R101.4.1 and R403.6, IECC 2018.
5. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the residential areas of the building. Reference: Sections R302.2 and R403.7, IECC 2018 as amended by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/28/2020 AMARTIN1 APPROVAL SHELF Completed