Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T20CM00312
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/07/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/07/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The make-up air requirement for residential clothes dryers located in a closet is an opening of not less than 100 square inches. Verify the total open area for an 18" x 6" Krueger S80H single-deflection grille. [Initial comment: Show how the dryer installations comply with Section 504.6, IMC 2018.] 2. Coordinate the roof components used for the envelope compliance with the components shown on the roof and building sections. Provide supporting documentation for the proposed U-factor for "concrete roof deck above batts: other roof". [Initial comment: Provide calculations for the building envelope to demonstrate compliance with the energy code; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. As a minimum, the information shall include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Use the commercial section of the 2018 IECC for the common areas of the building and the residential section of the 2018 IECC for the residential areas. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2018.] |
| 04/07/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/08/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/08/2020 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | FROM: Samuel Rogers PDSD Zoning Review Section PROJECT: T20CM00312 Benedictine Monastery Commercial Building Plan (2nd Review) 800 N Country Club Rd. TRANSMITTAL DATE: 4/8/20 DUE DATE: 5/1/20 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: Zoning has reviewed the building plans for compliance with the Development Package DP19-0165. The plans appear to match the building heights, footprint, square footage, and locations on the Development Package. All other commercial reviewers must approve the plans before zoning can approve. If you have any questions about this transmittal, Contact Samuel Rogers at (520) 837-6932 or at Samuel.Rogers@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
| 04/08/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/08/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |