Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T20CM00312
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/03/2020 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Multiple sheets contain the notation "Preliminary, not for construction". These sheets must be removed and replaced. Confirm sprinkler piping feeding fire pump is run overhead. Unclear from drawings. Per section 4.13.2.1.1.1 of the 2016 edition of NFPA 20, the passageway from the outside to the pump room must be 1 hour rated. This includes ceilings, rated self closing doors, etc. Verify and clearly indicate on plans. Indicate where on roofs the 2 1/2" hose valves will be. Review NFPA 14 for guidance. Please address these issues in a response letter. |
| 02/04/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/07/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T20CM00312 1. Sheet G002; Building Heights: A note indicates a horizontal assembly is provided at Level 2 per 510.2. Please add to that note that this condition is typical for all portions of the North building. 2. Sheet G003; Code Diagram 1 (Garage): A plan note indicates '22,991 NSF open parking S-2', followed by '23,632 NSF covered'. This would indicate more covered parking than there is actual parking. Please clarify. 3. Sheet G003; Floor Plans: Please indicate the means of egress and the exit access travel distances on the plans per the IBC Section 107.2.3, and verify the maximum distance indicated on Sheet G002 (195') is the worst case. 4. Sheet G401; Enlarged Pool Area: Is the pool, and all pool related structures, part of a separate permit? It was not included in the OK to Submit for the North Building, the South Building, or the Parking Structure. 5. Sheet G402; North Courtyard Site Plan: Is the north courtyard ramada (2/G402) part of a separate permit? It was not included in the OK to Submit for the North Building. 6. Sheet G403; East Walkway Ramada: Is the ramada (2/G402) part of a separate permit? It was not included in the OK to Submit for the North or South Buildings. 7. Sheets S4, S5, and S6: Which ramada do these drawings reference? Please indicate a reference on these drawings. 8. Sheet A-S303.1; Framing Plan: Framing Plan: The Plan Title indicates 4th Floor Framing. Is this the Roof Framing Plan? Please verify. 9. Sheet A-S303.2; Framing Plan: The Plan Title indicates 4th Floor Framing. The portion of the building on the west end is roof framing. Please verify. 10. Sheet A-S304.2; Framing Plan: The Plan Title indicates 5th Floor Framing. Is this the Roof Framing Plan? Please verify. 11. Sheet A-A100.0; Parking Floor Plan: The Sheet Title indicates Level 0, while the Floor Plan Title indicates Level 1-P. Please verify. 12. Sheets A-A101.2, A-A102.2, etc.: Several sheets are not sealed, signed, and dated by the registered design professional per the IBC Section 107.1. Please provide. 13. Sheet A-A121.2; Reflected Ceiling Plan: Please add a Key Plan to this sheet. 14. Sheets A-A121.3, A-A122.1, etc.; Reflected Ceiling Plans: Please add a Key Plan to these sheets. 15. Sheets A-A150, A-A151, etc.; Slab Plans: Please add a Key Plan to these sheets. 16. Sheet A-A501; Wall Type: Please indicate a U.L. Listing Number on Wall Types D1, D2, and D3. 17. Sheet A-A501; Wall Type B4: The one hour fire resistance rating provides a U.L. Listing Number, but the Wall Title indicates a two hour wall. Please verify. 18. General: Please provide dimensioned details for grab bars in restrooms/showers/tubs per the ICC/ANSI Chapter 6. 19. General: Please provide U.L. Listing Numbers for all rated slabs as required. 20. General: Are there any Special Inspections required for Site Preparation, Excavation, etc., that should be included on the Special Inspection Certificate? Please verify and add as required. 21. General: Please provide written responses to all review comments. Review by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 02/19/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Clarify the design of the waste and vent piping as shown on sheets A-P102.1 and A-P103.1. Sheet A-P103.1 clearly shows the waste piping for the 3rd level lavatories, showers and kitchen sinks dropping down to the 2nd level (sheet A-P102.1) where it is then being collected with the 2nd level horizontal waste piping for the lavatories, showers and kitchen sinks and then to four, 4" drops down to the level 0 in the garage (sheet A-P100.1). The waste from the water closets doesn't appear to be connected to anything and the referenced riser diagrams on sheet A-P006 seem to be unrelated to the drawings on A-P102.1 and A-P103.1. 2. Plumbing general note #6 calls for all sewer piping to run at 1/8" per 12" slope unless noted otherwise. Horizontal sewer pipes less than 3" require a minimum slope of ΒΌ" per 12". |
| 02/19/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/20/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The mechanical plan for unit 2B shows a dryer vent with a total equivalent length that is greater than 65-feet. Will a power ventilator be employed? Reference: Sections 504.8.4.1 and 504.8.4.3, IMC 2018. 2. Show how the dryer installations comply with Section 504.6, IMC 2018. 3. Provide mechanical ventilation for the residential areas of the building. Reference: Section R403.6, IECC 2018. 4. Provide calculations for the building envelope to demonstrate compliance with the energy code; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. As a minimum, the information shall include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Use the commercial section of the 2018 IECC for the common areas of the building and the residential section of the 2018 IECC for the residential areas. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2018. |
| 02/21/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet A-E200. Please apply the Keynote #2 on the site plan in the location it references. 2. Ref; Dwelling Units. (a) Include AFCI protection in Dwelling Unit Kitchens as required per NEC art 210.12A. (b) Verify that the luminaires over the showers or Bathtubs are rated for wet locations. NEC 410.10 3. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code for exterior lighting. 4. Provide compliance with the 2018 IECC. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
| 02/25/2020 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | FROM: Samuel Rogers PDSD Zoning Review Section PROJECT: T20CM00312 Benedictine Monastery Commercial Building Plan (1st Review) 800 N Country Club Rd. TRANSMITTAL DATE: 2/25/20 DUE DATE: 2/24/20 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: Zoning has reviewed the building plans for compliance with the Development Package DP19-0165. The plans appear to match the building heights, footprint, square footage, and locations on the Development Package. All other commercial reviewers must approve the plans before zoning can approve. If you have any questions about this transmittal, Contact Samuel Rogers at (520) 837-6932 or at Samuel.Rogers@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
| 03/02/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | 1) Once all oustanding commercial reviews are complete Engineering will conduct a final review of the building plans for consistency against the approved Development Package 2) Please update the plan set to include the approved version of the Development Package 3) Ensure that all roof drains scupper under pedestrian circulation areas |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/07/2020 | KROBLES1 | OUT TO CUSTOMER | Completed |