Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM00159
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/28/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/03/2020 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The copy of the plans is too blurry to read the text. Please submit a copy of the plans that are clear and legible. IBC 107.2.1. 2. Provide references to the key notes on the 1-line and 3-line diagrams. Specify the conductor sizes of feeders and branch circuits, and specify raceway sizes and descriptions. NEC 110.3. 3. The sheet with the 3-line diagram has information that was cropped off. Please verify and resubmit complete sheets with all of the required information. NEC 110.3. 4. Where the line side tap occurs, provide a letter from the manufacturer of the service equipment that allows the use of a line side tap while maintaining the product listing, or contact a nationally recognized listing agency to inspect and re-list the equipment. NEC 230.82. 6. The equipment specifications did not copy clearly, the text cannot be read; also, the sheet which contains the equipment specs. and placards has been cropped with information missing. NEC 110.3. |
| 02/03/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 02/05/2020 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
| 02/05/2020 | IMONSHI1 | ZONING | REVIEW | Reqs Change | FROM: Iman Monshizadeh PDSD Zoning Review Section PROJECT: T19CM00159 - Roof Mounted solar for AZ Cine Equipment Building Plan Review (1st Review) 2125 E 20TH ST/ I-1 Zoning TRANSMITTAL DATE: February 5th, 2020 DUE DATE: February 28th, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the building plans for compliance. Zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans. 2. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers, the building plans can be approved by zoning. If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/10/2020 | AMARTIN1 | OUT TO CUSTOMER | Completed |