Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20BU00582
Parcel: 11504475B

Address:
1055 N PARK AV

Review Status: Completed

Review Details: POOL - SPA

Permit Number - T20BU00582
Review Name: POOL - SPA
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2021 SBLOOD1 ENGINEERING REVIEW Passed
02/04/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide structural calculations for the pool and spa designs.
2. General: Sheet SP-005 does not bear the seal and signature of the engineer in responsible charge.
3. General: There are two SP-102 sheets indicated on the drawings. SP-103 is missing.
4. General: Please provide a Special Inspections Certificate with Parts A and B completed.
5. General: Please provide written responses to all review comments.
02/04/2021 LSHAMIS1 ZONING REVIEW Passed