Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: The project submitted indicates on Sheet SP-00 that this is for Gramercy-Safari Phase 2 in Scottsdale, AZ. Please submit appropriate drawings with changes as requested on the last review.
2. General: Please provide written responses to all review comments.
04/03/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide backflow protection for the pool and spa autofill sources.
2. Clarify the minimum acceptable size for the floor sink drain line; the note on sheet SP-101, "Items Not Supplied by Pool Contractor", shows X".