Plan Number: T19PI00004
Parcel: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T19PI00004
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2019 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved NO COMMENTS PER JIM FEMLING
02/28/2019 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Completed
02/28/2019 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved Street Maintenance irrigation runs parallel with 22nd St. in the city right of way. Any driveways would need to be sleeved, and any modification or damages would need to be repaired by the contractor. Call Paul Rosenboom with any questions (520)419-7064
02/28/2019 ERNIE ENCINAS DOT_ELEC REVIEW Completed
02/28/2019 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
02/28/2019 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed
02/28/2019 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Completed
02/28/2019 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
02/28/2019 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Completed
02/28/2019 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
02/28/2019 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Completed
02/28/2019 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Completed
03/08/2019 GARY WITTWER DOT LANDSCAPE REVIEW Approved
03/20/2019 ZELIN CANCHOLA DOT TRAFFIC REVIEW Approv-Cond March 20, 2019

SUBJECT: Encantada at Rita Ranch T19PI00004 (I-2019-003)


PROJECT REVIEWER: Zelin Canchola,
TDOT Review Section

RESUBMITTAL REQUIRED: DOT Review Section has reviewed the PIA Plan for Traffic Engineering. The proposed plan is acceptable however it requires the following change for a conditional approval. Changes can be submitted in a PDF to expedite approval.

Page 7 of 7

1. Eliminate crosswalk and stop bar striping

2. Change - place supplement "right turn" RF-5F on top of Right turn signs.

3. Add striping quantities.

If you have any questions I can be reached at 837-6659 or zelin.canchola@tucsonaz.gov
03/26/2019 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
03/26/2019 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change March 25, 2019


SUBJECT: Offsite Improvement Plans for La Encantada at Rita Ranch (Valencia Rd)

PROJECT REVIEWER: Richard Leigh, TDOT, TDOT Eng. Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and recommends a conditional approval at this time. The following comments need to be addressed and plans revised prior to submitting mylar plan set for signatures. Please submit a PDF copy for review prior to submitting mylars.

1. Include the plan number "I-2019-003" in the title block of each sheet.

2. Include the PIA activity number "T19PI00004" on cover sheet.

3. Sheet 2, General Paving Note 3: Revise note to indicate the use of COT Mix No. 2 for the asphaltic concrete.

4. Sheet 2: Revise roadway sections to indicate the placement of 6' wide sidewalk along Valencia Rd. pursuant to section 10-01.4.1.A.1.a of the Technical Standards Manual.

5. Sheet 3: Revise drawing to indicate that the cross slope in the pedestrian crosswalk areas at the driveways will not exceed 2%.

6. Sheet 4: Revise drawing to relocate curb access ramp on the east side of the east driveway south to be more in line with west ramp. Pursuant to AZ Revised Statute 9-499.02 ramps must align with each other where the cross the street.

7. Sheet 4, Sections 2 & 3: Indicate type of filter fabric. Filter fabric shall be Mirafi 140N or an equivalent type.

8. Sheet 5: Verify P.A.G. Standard Detail called out for proposed catch basin and indicate wing lengths.

9. Sheet 5: Provide an additional manhole in the storm drain run within Valencia Road. Pursuant to S.M.D.D. Section 10.9.1.8, a minimum 300 Ft minimum manhole spacing is recommended for conduits 30 In. or less.

10. Sheet 6: Provide a longitudinal section for the 3 - 30 In storm drains crossing Valencia Road.

If you have any questions, I can be reached at 837-6647 or emailed at Richard.Leigh@tucsonaz.gov.
03/26/2019 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed