Permit Number: T19CM09337
Parcel: 104092250

Address:
4241 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM09337
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2020 DJELLEN1 ZONING REVIEW Reqs Change FROM: David Jellen
PDSD Zoning Review Section

PROJECT: T19CM09337 - New Food Service - Panda Express
Building Plan Review (1st Review) / Relate to DP19-0310
4241N. Oracle Road / C-3 Zoning

TRANSMITTAL DATE: March 17, 2020

DUE DATE: March 31, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Provide the applicable setbacks from the building to the property line. Ensure that the plan is consistent with what is being proposed in the development package.


2. COMMENT: Zoning has reviewed the building plans for compliance with the unapproved development package. Zoning cannot approve the building plans until the development package has been approved. Additionally, zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.


3. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.


4. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, contact David Jellen at (520) 837-4082 or by email at David.Jellen@tucsonaz.gov.
03/20/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/25/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The PDF for the Outdoor Lighting lumen Calculations submitted does not correlate with the lumen calculations on the site lighting plan E-105. Also the calcs are incorrect. Revisit table 401,1 for lumens allowed.
2. For clarity, please include the luminaire schedule for the exterior lighting including the canopy luminaires on the site plan E-105. Correlate the mark for the luminaires shown at their locations on the site plan with the luminaire schedule and the lumen calculations.
3. Provide shielding, and lamp color temperature information on the luminaire schedule or provide manufacturer cut sheets.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
03/25/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change ASSE 1012-rated backflow preventers are designed for use in low hazard situations. What is the nature of the chemical additive (i.e. will it cause an actual hazard to the public health if it is introduced into the water distribution system through a backflow event). [Initial comment: The McDonalds model 205S inline check valve (Chemical feed system detail, P-400) does not appear to have an ASSE listing as a backflow protection device. Provide a backflow protection device that is listed for the intended application. Reference: Sections 608.6 and 608.7, IPC 2018.]
03/26/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/31/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change DP must be approved first.