Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM09337
Parcel: 104092250

Address:
4241 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T19CM09337
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
01/06/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change T19CM09337

1. Sheet G-001; Plumbing Fixtures Table: Per the IBC Table 2902.1, please add the service sink requirement to the Plumbing Fixtures Table.
2. Sheet G-001; Building Code Analysis: The required egress width calculation uses 79 occupants rather than the 84 occupants listed. Please verify.
3. Sheet G-001; Occupant Load Calculation; Panda Express Summary: The occupant load calculation indicates 74 occupants for the building interior and 10 occupants for the outdoor dining, while the Panda Express Summary indicates 68 indoor seating and 16 outdoor seating. Please coordinate.
4. Sheet A-105; Reflected Ceiling Plan: A canopy is indicated on exterior walls with a note that it is to be provided by the general contractor. Is a dimension for the various canopy sizes provided on any plan, detail, or note? Please verify.
5. Sheet A-107; Roof Plan Keynotes: Note R1 was not located on the plan. Please verify.
6. Sheet A-109; Furniture Plan: The outdoor dining area is not indicated on this plan. Please provide that plan along with the seating layout.
7. Sheet A-200 (North Elevation); Sheet A-303 (Section 2): It appears the canopy is not indicated on Section 2/A-303 as indicated on the elevation. Please verify.
8. Sheet A-201 (East and West Elevations); Sheet A-400: A Detail 10/A-400 is cut on the elevations. Please revise the detail call-out, or add that detail to Sheet A-400.
9. Sheet A-302; Sections 2 and 3: Please complete the detail reference at the window sills.
10. Sheet A-302; Section 2: A wall detail at the canopy indicates 06/A-400. Should this be marked as SIM? Please verify.
11. Sheet A-402; Detail 2: A note indicates low wall construction by contractor. The construction of this wall must be shown on the drawings for inspection purposes. Please provide that information on the detail.
12. Sheet S-101; Roof Diaphragm Detail 2: Note 2 indicates to reference the plan for the roof nailing size and spacing. Please revise that note (nailing is called out on Detail 2).
13. Sheet S-101; Roof Framing Plan: A note on the west wall (near Section cut 13/S-300) indicates 6x6 blocking per Section 19/S-300. Section 19/S-300 references Section 9/S-300, which references 2/S-300. Section 2/S-300 does indicate 4x6 blocking, but 6x6 blocking is not referenced on any of these sections. Please verify.
14. General: Please provide the Special Inspection Certificate with Parts A and B completed. This form may be found on the City of Tucson website (www.tucsonaz.gov/PDSD).
15. General: Please provide written responses to all review comments.

Review by Eric Newcomb (Eric.Newcomb@tucsonaz.gov)
01/16/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The design of the water heater piping (detail 5/P-400), with a shutoff valve located between the water heater and the expansion tank, makes it impossible for the expansion tank to accommodate the thermal expansion of the water in the water heater, as intended by Section 607.3, IPC 2018. Reference: Section 303.2, IPC 2018.
2. The McDonalds model 205S inline check valve (Chemical feed system detail, P-400) does not appear to have an ASSE listing as a backflow protection device. Provide a backflow protection device that is listed for the intended application. Reference: Sections 608.6 and 608.7, IPC 2018.
3. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.1, IPC 2018.
4. Air admittance valves are not approved for use in a combination waste and vent system. Reference: Section 918.3, IPC 2018.
5. Provide a vent downstream of the gravity grease separator to protect the seal for the grease separator. Reference: Sections 303.2 and 1003.9, IPC 2018.
01/16/2020 DJELLEN1 ZONING REVIEW Reqs Change FROM: David Jellen
PDSD Zoning Review Section

PROJECT: T19CM09337 - New Food Service - Panda Express
Building Plan Review (1st Review) / Relate to DP19-0310
4241N. Oracle Road / C-3 Zoning

TRANSMITTAL DATE: January 16, 2020

DUE DATE: January 27, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package. Zoning cannot approve the building plans until the development package has been approved. Additionally, zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.


2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact David Jellen at (520) 837-4082 or by email David.Jellen@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
01/16/2020 ROBERT SHERRY WATER REVIEW Completed
01/17/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. This project is under the jurisdiction of the City of Tucson, not Apache Junction (see keynote #267, M-100).
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018.
3. Show how the HVAC controls are capable of reducing the outside air to the minimum flow rates required by Chapter 4, IMC 2018. Reference: Section C403.2.2, IECC 2018.
4. Verify that the specified HVAC systems are provided with controls that are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy. Reference: Section C403.4.2.3, IECC 2018.
5. Show that the walk-in cooler and walk-in freezer meet the efficiency requirements of Section C403.10.2.1, IECC 2018.
01/24/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code.
This code can be printed or downloaded from www.tucsonaz.gov/pdsd.
2. The site plan should include;
(a) Locations and identification of all exterior lighting on the parcel that also correlates with the luminaire schedule and lumen calcs, including canopy lighting.
(b) Show the lighting area and option used per table 401.1.
(c) Parcel size in acres.
(d) Total allowed unshielded and full cut off lumens per acre.
(e) Total proposed unshielded and or full cut off lumens.
(f) Lamp color temperature output (not to exceed 3500K) per 402.1.
(g) A note stating whether or not a special inspection is required. 104.2.2, 106.2.1.

Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
01/29/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change DP MUST BE APPROVED FIRST.
12/31/2019 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/05/2020 AMARTIN1 REJECT SHELF Completed