Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM08781
Parcel: 117081040

Address:
834 S 6TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM08781
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the service hot water distribution systems for the residential units per Section R403.5.1, IECC 2018.
2. Clarify the relationship of the water calculations to the booster pump schedule (i.e. if the booster pump discharge is set to 58 PSI, how does the building have 71 PSI available?). Reference: Section 107.2.1, IBC 2018.
3. Verify the locations of the proposed indirect waste receptors (R-5) are visible for inspection and have ready access for cleaning. Reference: Section 802.4, IPC 2018.
4. The connection of the horizontal drain from the two 2nd floor lavatories to the vent for the two back-to-back water closets in Unit A (Detail A/P-7) is not allowed. It is not clear if a similar issue is occurring in the 2nd floor of Detail B/P-7 where the horizontal drain for R-1A may be connecting to the vent for R01B or for the 1st floor connection of -1A and -1B in Detail D/P-7. Reference: Section 901.4, IPC 2018.
5. Show how secondary roof drainage is being provided. Reference: Section 1108.1, IPC 2018.
01/03/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show how the dryer installations in the D, E, and F units comply with Section 504.6, IMC 2018.
01/08/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change 1) Engineering can approve the plans after all commercial reviews have been approved
12/10/2019 MARTIN BROWN FIRE REVIEW Approved
12/13/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0.1; Project Information (Building Information): The automatic sprinkler system indicates "NFPA13R per". Please finish that requirement.
2. Sheet A0.1; Applicable Codes: Please add the 2018 International Existing Building Code to the list of codes.
3. Sheet A0.2; Stair Detail 3: A note indicates to "See structural for guardrail detail". Please verify that detail with guardrail requirements in on a structural sheet.
4. Sheet A0.2; Stair Detail 3: Per the IBC Section 1011.8, a flight of stairs shall not have a vertical rise greater than 12' between floor levels. Please verify the vertical rise is not greater than 12' (detail indicates +/- 12'-0"), or indicate an intermediate landing.
5. Sheet A0.5; Floor Plan: Please verify on this plan that the shell spaces are not sprinklered. It does not appear the drawings indicate sprinklers in those two spaces. The IBC Section 508.3.1 requires the most restrictive provisions of Chapter 9 to be applied to the entire nonseparated occupancy area. Please verify.
6. Sheet A2.1; West Elevation Keynotes: Note 5 indicates to provide 3 handrails per the IBC Section 1014. That section indicates handrails must be located so that they are within 30" of all portions of the stairway minimum width. Please verify these handrails meet that requirement.
7. Sheet A2.2; Section #2 Keynotes: Note 13 references Detail 1 on Sheet A0.2 for a handrail. Please revise that reference.
8. Sheet A4.1; Elevation "D": Please provide the vertical dimension above the floor for the vertical grab bar per the ICC/ANSI Figure 604.5.1.
9. General: Per the International Existing Building Code Section 605.2, this project must comply with the provisions of Chapter 10. Please indicate this requirement on Sheet A0.1, and verify all requirements of that chapter are met.
10. Sheet S3.0; Floor Framing Plan: On the east wall, two detail cuts indicate 212A. There is no Alternate A indicated on that detail. Please verify.
11. Sheet S3.0; Floor Framing Plan: At the southwest corner of the building, a detail cut indicates 203. Please verify. Is this a masonry wall?
12. Sheet S5.0; Detail 204: A note at the bent plate indicates "bent plate per schedule". Please verify where this schedule is located.
13. General: Please provide a Special Inspection Certificate with Parts A and B completed.
14. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
12/17/2019 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: T19CM08781 - Flash TV North TI - Mixed Use
Building Plan Review (1st Review) / Relate to DP19-0217
1202 E Broadway / C-3 Zoning

TRANSMITTAL DATE: December 17th, 2019

DUE DATE: December 24th, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package. While the building plans are consistent with the approved DP as it relates to the zoning review purview of the Building footprint, Height, square footage, site conditions etc., zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
12/24/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E1.0. Change the electrical note reference for the 2011 NEC to 2017.
2. Show the location of electrical Service #2 and #3 on the site plan. Identify Service #1.
3. Ref; Plan Sheet E-6.0. There is a note at the grounding detail referencing the #4 cu that states, "REFER TO 2/0E1.3". Please clarify.
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/22/2020 AMARTIN1 REJECT SHELF Completed