Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G100; Plan 4: A note references ANSI A117.1 2003 (603.2.3) Exception #2 for an inward door swing. Please revise to the 2009 Edition Section 603.2.2 Exception 2.
2. Sheet G102; Code Analysis (Exit Travel Distance): The Room Door to Exit Travel Distance indicates 150'-0" and references the IBC Table1017.2. Does that Table provide the Room Door to Exit Travel Distance, or is there another IBC Section with that requirement? Please verify.
3. Sheet A101 (Floor Plan); Sheet A501 (Type 1 Partitions): The Partition Type 1F3-1 (Paint/Flammable Rooms) is not included in the Type 1 Partitions list. Please verify.
4. Sheet A101; Keynote Legend: Note 6 indicates to uprate a one hour partition to a two hour partition. Please indicate the U.L. Listing Number for that two hour partition in Note 6.
5. General: Please provide written responses to all review comments.
12/04/2019 PAUL CAMARENA ZONING REVIEW Approved
12/10/2019 MARTIN BROWN FIRE REVIEW Approved
12/17/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1.Provide load calcs for panel 'SIN-B04' to verify its capacity for the new load.
2. Provide complete compliance with the 2018 IECC for the lighting.
Ref; 2018 IBC 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements. Can be printed or downloaded from (www.tucsonaz.gov/pdsd).
12/17/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a fire damper for the return air penetration 2-hour rated partition on the west wall of the Keyshop.
2. The fire damper symbol for the exhaust duct penetration of the Paint/Flammable Storage room has been obscured by the duct size note.
3. The air balance calculations for the general shops room shows 4,000 CFM supply, 1250 CFM return, 2600 CFM exhaust and 150 CFM of excess air. The balancing data on sheet MH101 however shows 4,000 CFM supply, 1250 CFM return and 500 cfm exhaust. The two dust collectors appear to be returning their airflow to the room and there is no description of where the 2750 CFM of excess air might be flowing. Coordinate the air balance for the room and show where the airflow through the louvers goes.
4. The ventilation calculations categorize the general shops room as "wood/metal shops" based on Table 403.3.1.1, IMC 2018 and list the outdoor air rate for people at 10 CFM per person and the area outdoor air rate at 0.18 CFM/SF as shown in the table. The zone population however is listed at only 10 people compared to the 50 people called for in the table. The calculations omit the 0.5 CFM/SF of exhaust required for this occupancy type and also omit consideration of the applicable footnote (g) in the table. Footnote (g) requires that any supply airstream consist of less than 10% of the recirculated air from the shop. Provide justification for the zone population, provide the required exhaust flow rate, and verify the contribution of the return air to the supply airstream.
12/17/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/19/2019 SBORZAK1 OUT TO CUSTOMER Completed