Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM07637
Parcel: 13824083A

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T19CM07637
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 2; Egress Travel: Per the IBC Section 1017.3, the exit access travel distance shall be measured from the most remote point of each area along the natural and unobstructed path of horizontal and vertical (not diagonal) egress travel to an exit. Please revise, and indicate the travel distances meet the requirements of the IBC Table 1017.2.
2. Previous Comment 4; Drinking Fountain (A/A-4): Per the ICC/ANSI Section 602, the drinking fountain must be a high/low for wheelchair accessibility and for standing persons (see Figure 602.5b). Please revise and indicate/call out the drinking fountain on Sheet A.2.
3. Previous Comment 5; Service Sink: Please indicate/call out the service sink on Sheet A.2.
4. General: Please provide written responses to all review comments.
07/10/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the source of the tempered water. WH-2 is scheduled on sheet P2 but the north restroom shows WH-1 installed; the water heater for the south restroom is not labeled. Detail B/P-1 does not indicate that a point-of-use water heater is being used. [Initial comment: Show how tempered water will be provided to the lavatories.]
2. Comment not resolved. CPVC piping is not mentioned on the new drawings; PEX and Type L copper are the only water piping materials called out on the drawings. The support requirements are noted only for copper and steel pipe. [Initial comment: Note how the overhead water distribution piping will be supported.]
3. Provide the distance from the property line to the new propane storage tank. Reference: Section 107.2.1, IBC 2018.
4. Show the number, size, and placement of the bollards protecting the new propane storage tank.
5. Assuming that you have used the branch length method for determining the pipe sizes for the propane distribution (Section 402.4.2, IFGC 2018), the branches to the two unit heaters furthest to the north are under-sized. They need to be 1", not ¾". Reference: Table 402.4 (28), IFGC 2018.
6. Provide details for the installation of the unit heater vents. The details are to include the required dimensions from the heater to the exterior wall, the distance from the exterior wall to the listed terminal cap, size and slope of the vent, the type of vent pipe (i.e. single-wall or double wall), any required thimbles, and how the vent will be supported. Reference: Section 501.14, IFGC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/20/2020 KROBLES1 OUT TO CUSTOMER Completed