Permit Number: T19CM07637
Parcel: 13824083A

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T19CM07637
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Needs Review 1. Please show the location of all EXIT doors on the architectural floor plan. IBC 107.2.1.
2. Provide an egress plan and indicate travel distances from most remote location of the building to exit doors.
3. Provide an an exit plan that specifies the common path of egress travel along a travel route around equipment and obstructions. IBC 1006.2.1.
4. Drinking fountain(s) required for persons in wheelchairs and standing persons. IBC TABLE 2902.1
5. A service sink is required. IBC TABLE 2902.1
6. Provide a reflected ceiling plan and show the location of all EXIT signage and means of egress illumination. IBC 1008.2, 1008.3.
7. Provide framing details of the wall construction for the restrooms and power room. Indicate fastening and bracing to the roof/ceiling and floor slab.
8. Provide a room finish schedule: indicate wall cover materials for new walls and restrooms. IBC 1209.2.
9. Provide minimum plumbing fixture calculations for the occupancy. IBC TABLE 2902.1.
10. Indicate whether the building is sprinklered on the BUILDING CODE ANALYSIS testbox. IBC 107.2.1.
02/28/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide water service and drains for the evaporative coolers.
2. Provide vents for the plumbing fixtures.
3. Show how tempered water will be provided to the lavatories.
4. Provide specifications for the lavatory faucets.
5. Note how the overhead water distribution piping will be supported.
02/28/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/28/2020 LSHAMIS1 ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/04/2020 AMARTIN1 OUT TO CUSTOMER Completed