Permit Number: T19CM06808
Parcel: 10907006C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM06808
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2019 PAUL CAMARENA ZONING REVIEW Passed
09/26/2019 MASHFOR1 FIRE REVIEW Approved
10/04/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 2; Piping Plan: A gate note (Delta 1) indicates to construct per SD-1610 except as noted above. No reference was found in the Keynotes. Please verify.
2. Sheet 12 (Building Section C); Structural Calculations (Page 4): The structural calculation indicates a 10" maximum roof slab thickness. Please indicate that on the Building Section.
3. Sheet 12; Building Notes: The last sentence of Note 7 indicates "ALTERNATE CMU LINTEL". Please add to reference Detail B on this sheet for that cmu lintel.
4. Sheet 12 (Footing Table); Structural Calculations (Page 14): The calculations indicate a 1'-4" footing width, but the
Footing Table indicates a 12" footing width option. Please clarify.
5. Sheet 12; Building Section C: The Building Section shows 2-#4 at the top of the footing, while the Note 12 indicates 1-#4 at the top. Please coordinate.
6. Sheet 12; Building Notes: Note 13 references the Right Elevation for the reinforcement extension beyond the opening, and the Left Elevation for the reinforcement extension beyond the opening. The Right and Left Elevations have no openings. Please revise.
7. Sheet 12; Building Notes: Please clarify in Note 13 where the 14" or 24" reinforcement extension is applicable, and where the 20" or 24" reinforcement extension is applicable.
8. Sheet 12; Building Section C: Please add the 2-#4 at the top of the footing on the right side of the Building Section (per Note 12).
9. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
10/14/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/14/2019 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Completed
10/14/2019 RMCCOY1 PLUMBING-COMMERCIAL REVIEW Passed
10/17/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/08/2019 SBORZAK1 REJECT SHELF Completed
10/17/2019 SBORZAK1 APPROVAL SHELF Completed
10/17/2019 SBORZAK1 OUT TO CUSTOMER Completed