Permit Number: T19CM06754
Parcel: 13824162A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM06754
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

The resubmittal was insufficient to determine full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. Ordinance # 10963.

Please update the lighting plans with the following information on the plans as required per section 104 (plan submittal requirements);

Revise the Outdoor Lighting Calculations to show the lighting area and correct option. See Table 401.1.

Indicate the parcel size in acres.

Total lumens allowed per table 401.1 vs total final lumens including existing lighting on the property.

Luminaire schedule must correlate with luminaires shown on the site lighting plan.

Indicate light source color temperature output and shielding for all exterior luminaires including under canopy .

Provide luminaire manufacture cut sheets with the luminaire specified.

Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

Specify any exceptions used.

Curfew lighting controls If applicable.

Do not confuse the Outdoor Lighting Code with the IECC.

Ref; 2018 IBC 107.2.1, 2017 NEC, Tucson/Pima County Outdoor Lighting Code. City of Tucson Commercial Plan Submittal Requirements.