Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM06141
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/28/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 4; Sheet A2.0 (Floor Plan); Sheet E1.1 (Floor Plan 2): The electrical floor plan indicates one new transformer, while the architectural floor plan indicates two. Please coordinate. There is still one transformer indicated on Sheet A2.0 (near Grids 1 and N) that does not show up on Sheet E1.1. |