Permit Number: T19CM06141
Parcel: 14108521E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM06141
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/26/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/26/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/26/2019 ROBERT SHERRY WATER REVIEW Completed
08/26/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0.0; Deferred Submittal: A deferred submittal will be required for the new stair. Please indicate on this sheet.
2. Sheet A2.0; Keynotes: Note 6 indicates a new 15'-0" opening in the existing demising wall. Please provide details on this sheet for that opening, and structural calculations as required.
3. Sheet A2.0 (Keynotes); Sheet E1.1 (Floor Plan 2): The electrical floor plan indicates a floor mounted transformer, while Keynote 9 on Sheet A2.0 indicates a wall mounted transformer. Please coordinate.
4. Sheet A2.0 (Floor Plan); Sheet E1.1 (Floor Plan 2): The electrical floor plan indicates one new transformer, while the architectural floor plan indicates two. Please coordinate.
5. Sheet A2.0; Detail 3: Please provide the base plate size and the quantity and size (diameter and length) of the expansion anchors on this detail.
6. General: Please provide written responses to all review comments.
08/26/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/27/2019 MRESS1 ENGINEERING REVIEW Passed
08/27/2019 MALLORY RESS ZONING REVIEW Approved
08/27/2019 MROSS2 FIRE REVIEW Reqs Change Will need an analysis of the fire sprinkler system by an FPE to determine if an upgrade will be required.