Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM06136
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/05/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Calculate the number of required plumbing fixtures for the enlarged building. Reference: Section 2902.1, IBC 2018. 2. Provide roof drainage calculations and plans. Provide overflow protection for the roof. Reference: Sections 1101, 1106 and 1108, IPC 2018. |
| 09/05/2019 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. |
| 09/06/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code. Reference: Sections C103.2, C303, and C502.1, International Energy Conservation Code 2018. 2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1, IECC 2018. 3. The City of Tucson has not adopted ASHRAE Standard 62-1 as an approved method for calculating ventilation requirements. Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2018; for HVAC systems serving multiple zones (e.g. HP-1 and HP-2), see Section 403.3.1.1.2.3, IMC 2018. |
| 09/11/2019 | IMONSHI1 | ZONING | REVIEW | Passed | |
| 09/16/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the code analysis for the minimum number of required plumbing fixtures , and note on plan.IBC Chap 29, IBC Table 2902.1. 2. Provide the code analysis and calculations for the occupant load and calculate using all occupancies - F-2 , B , and A-3 , correct the occupant load on plans , IBC 1004. 3. Provide the code analysis for the egress width provided and correct on plans.IBC 1005. Respond to plan review comments in writting . |
| 09/20/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Verify that a 125v receptacle is within 25' of the mechanical equipment for servicing. If not provide as necessary. NEC 210.63. Ref; 2018 IBC sec 107.2.1, 2017 NEC. 2012 Tucson/Pima County Outdoor Lighting Code |
| 10/07/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed |