Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T19CM06052
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/07/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/22/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet E-3. As requested per the previous plan review….Show grounding for the new 200 amp electrical service. NEC 250. Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/03/2019 | QJONES1 | OUT TO CUSTOMER | Completed |