Review Details: CELL TOWER/ANTENNAS
Permit Number - T19CM06052
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/12/2019 | PMARTIN1 | COMMUNICATIONS | REVIEW | Approved | |
09/27/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet LS-2; Survey Detail: A note on this plan indicates a "Proposed Tower". Please verify if this is a new or existing cell tower and foundation. 2. Sheets A-1 and A-2; Site Plans: These plans indicate an existing 45'-0" monoelm. Please verify if this is a new or existing cell tower and foundation. 3. General: This permit appears to include drawings for a new drilled pier foundation, and drawings and calculations for a new cell tower. Please verify if this is a new or existing cell tower and foundation. 4. General: It appears this is an existing cell tower with an existing foundation. Please verify. If the calculations provided are for existing elements, please indicate on the calculations and on the drawings that the existing tower and foundation (as built) are adequate for the addition of the new antennas. 5. General: Please provide written responses to all review comments. Review by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
10/04/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please include a grounding detail for the new 200 amp service equipment. NEC 230, 250. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/28/2019 | AMARTIN1 | OUT TO CUSTOMER | Completed |