Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2019 SAMUEL ROGERS ZONING REVIEW Approved
08/15/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1.Coordinate the mechanical design shown on sheet M1 with the heating/cooling load calculations, the mechanical COMcheck, and sheet P1.
2. Provide the rational for determining the ventilation requirement for the workroom. Reference: Section 403.3.1.1, IMC 2018.
08/15/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/15/2019 SROGERS2 ENGINEERING REVIEW Passed
08/15/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Roof Plan: Please provide structural calculations for the existing roof structure at the new heat pump (see Sheet M1).
08/15/2019 ROBERT SHERRY WATER REVIEW Completed
08/15/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Coordinate sheet P-1 (condensate drains) with the mechanical design.
08/15/2019 MARTIN BROWN FIRE REVIEW Approved
08/15/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed